OFF Grid Journal

How to connect an inverter to a battery: short cables, a fuse at the terminal, then a load test

Two heavy cables and one fuse. Most of the safety is in how short, how tight and how close.

A hand tightening the cable lugs on a wall-mounted inverter with a wrench, heavy red and black cables looping below
Photo from The Off-Grid Handbook.
In this article
  1. What you need before you start
  2. Inverter wiring diagram, in words
  3. How to connect an inverter to a battery, step by step
  4. Inverter battery cable size
  5. Never connect the inverter to house wiring
  6. Safety while you work
  7. Frequently asked questions

Here is how to connect an inverter to a battery safely. Mount it within 3 to 6 feet of the battery, run short, heavy cables sized per the inverter's manual, and put a fuse on the positive cable within inches of the battery terminal. Connect positive to positive and negative to negative, torque the lugs, then load-test at half and full rating before you rely on it.

Those are steps 3 to 5 of Project 22 in The Off-Grid Handbook, a job the book puts at about two hours and $80. Sizing comes first and has its own guide, what size inverter do I need. This one is the hookup.

What you need before you start

The battery side should already be built and fused, like the book's LiFePO4 battery box. If you have a fuse and disconnect board from Project 26, the inverter feed lands there on its own labeled fuse.

Inverter wiring diagram, in words

ConnectionFromTo
Positive cableBattery positive terminalFuse within inches of the terminal, then the inverter's positive terminal (through the disconnect, if you have one)
Negative cableBattery negative terminalThe inverter's negative terminal
GroundInverter chassis ground lugAs the inverter manual directs
LoadsInverter AC outletsPlugged in directly, never into house wiring

The fuse goes at the battery end because that is where the energy is. The Florida Solar Energy Center (FSEC) at the University of Central Florida warns that batteries can deliver thousands of amperes in a short circuit. A fuse at the terminal protects the whole length of cable behind it.

How to connect an inverter to a battery, step by step

  1. Keep the circuit open while you work. Leave the inverter switched off, and leave the fuse out or the disconnect off until the last step.
  2. Mount the inverter within 3 to 6 feet of the battery on a ventilated board, in a dry spot with air around it.
  3. Crimp the lugs onto cable cut as short as the layout allows, with the cable size from the manual.
  4. Mount the fuse holder on the positive cable, within inches of the battery terminal.
  5. Make the connections at the inverter first, then at the battery, red to positive and black to negative. Check polarity twice before the circuit is closed.
  6. Torque the lugs to the figure in the manual. The book's warning: loose high-current connections are heat sources.
  7. Close the circuit by installing the fuse or turning on the disconnect, then switch the inverter on.
  8. Load-test at half and full rating. After ten minutes, check the cable temperature by hand. Warm is normal; hot is a fault.

If anything is hot, switch off, open the circuit and look for a loose lug or undersized cable before you try again.

Choosing the spot

The book asks for a ventilated mounting board, and the reason is heat: an inverter warms up as it works, and most have a fan or cooling fins that need open air. Pick a dry place, off the floor, where the cooling vents are not blocked and nothing will be stacked against it. Close to the battery matters more than convenient to the couch; run an extension cord from the inverter's outlet to the device rather than lengthening the heavy DC cables.

Check it again later

Heavy connections can settle. After the first week of use, open the circuit and recheck the lugs for tightness and the cables for any sign of heat. Then add the inverter to your binder notes with its fuse size and cable size, so whoever services the system next has the numbers.

Inverter battery cable size

An inverter pulls a lot of current from a 12 V battery. The arithmetic is simple: 600 watts ÷ 12 volts = 50 amps before conversion losses. Sandia National Laboratories' guide to photovoltaic systems and the National Electrical Code notes that a 2,000 W inverter on a 12 V system can draw more than 235 amps at full load.

FSEC's rule for battery conductors is that they should handle at least 125% of the maximum current and keep voltage drop generally under 5%, with particular attention to the high-current run between battery and inverter. That is why the book says short and thick, and why the cable size in your inverter's manual is the one to use. Our guides to 12 V wire gauge and inverter fuse size show the math behind those figures.

Keeping the inverter within 3 to 6 feet is part of the same rule. Every extra foot of heavy cable adds resistance, and resistance turns into heat and lost power.

Never connect the inverter to house wiring

The book's safety box for this project is written in plain terms: inverter output is real 120 V AC and can kill exactly like a wall outlet. Never wire it into household wiring or an outlet. That is backfeeding, and it endangers utility line workers.

Loads plug into the inverter directly, full stop. If you want power in house circuits, that takes transfer equipment installed by a licensed electrician under the National Electrical Code. The same rule applies to generators; see why a generator never plugs into a wall outlet.

Safety while you work

The NFPA notes that there is essentially no way to make an operating battery electrically safe, so working on a battery should always be treated as energized electrical work. The Handbook's rules for battery work follow from that:

Add a battery disconnect switch so you can shut the system down without pulling cables, and make sure the inverter you bought is the right type: see pure sine wave vs modified sine wave. When nothing needs AC, switch the inverter off and save the battery for the loads that matter.

Frequently asked questions

How far can an inverter be from the battery?

The Off-Grid Handbook says to mount it within 3 to 6 feet of the battery, with cable runs kept short. Inverters draw high current at 12 V, so every extra foot of cable adds resistance, heat and voltage drop. Use the cable size in your inverter's manual.

Where does the fuse go between an inverter and a battery?

On the positive cable, within inches of the battery terminal. The book specifies a Class T or ANL fuse sized to the inverter. Placing it at the battery end protects the whole cable, since a battery can deliver thousands of amperes into a short circuit.

What size cable do I need to connect an inverter to a battery?

Use the size the inverter manual gives. As a reference, the Handbook pairs 4 AWG cable with a 600 W inverter, kept short. The Florida Solar Energy Center advises sizing battery conductors for at least 125% of the maximum current and keeping voltage drop generally under 5%.

Can I connect an inverter to my house wiring?

No. Wiring inverter output into household wiring or an outlet is backfeeding, which can energize utility lines and endanger line workers. Plug loads directly into the inverter. Powering house circuits requires transfer equipment installed by a licensed electrician.

Sources

Safety guidance changes. Check the agency pages above for the current version, and follow your local code and manufacturer instructions.