OFF Grid Journal

Inverter fuse size: how to work it out from the manual, the cable and the battery

The right number is printed in your inverter's manual. Knowing where it comes from helps you spot a wrong one.

Gloved hands cutting heavy red cable in a basement workshop below a wall board of large cartridge fuse holders
Photo from The Off-Grid Handbook.
In this article
  1. Inverter fuse size: what the fuse has to do
  2. What size fuse for an inverter: the math manuals use
  3. Inverter fuse size chart: what to look up instead
  4. Class T or ANL?
  5. Where the inverter fuse goes
  6. When an inverter fuse blows
  7. Frequently asked questions

The right inverter fuse size is the one your inverter's manual specifies for your battery voltage, installed on the positive cable within inches of the battery terminal. Manuals arrive at that number the same way: the inverter's maximum continuous DC input current, plus headroom, and never more than the cable can carry.

The Off-Grid Handbook lists "Class T or ANL fuse sized to the inverter" among the materials for Project 22, and places it on the positive within inches of the terminal. This guide does not print a one-size fuse chart, because inverter efficiency, input voltage and cable differ from model to model. It shows you the math, so you can check the manual's figure against your own setup.

Inverter fuse size: what the fuse has to do

An inverter fuse has two jobs that pull in opposite directions:

Sandia National Laboratories' guide to photovoltaic systems and the National Electrical Code sets the limit on the second job: the rating of the overcurrent device should always be less than or equal to the ampacity of the cable, the current the cable can carry without overheating. The fuse protects the wire, not the inverter.

Sandia also notes that inverters are not counted as overcurrent devices. An internal fuse or shutdown inside the inverter does nothing for the cable between it and the battery.

What size fuse for an inverter: the math manuals use

Sandia works through an example. A 2,500 W inverter on a 24 V system, at 85% efficiency and 22 volts, draws 134 amps at full load. The cables between battery and inverter must carry 125% of that, or 167 amps. The general pattern is:

  1. Continuous watts ÷ (low battery voltage × efficiency) = full-load DC current.
  2. × 1.25 for the cable's minimum ampacity.
  3. Fuse rating: at or above the inverter's full-load current, and at or below the cable's ampacity, as the manual specifies.

For the book's 600 W inverter on 12 V, step one starts at 600 ÷ 12 = 50 amps before losses, and real current is higher once efficiency and a sagging battery are counted. That figure is a check on the manual, not a replacement for it.

Why the fuse does not blow on startup

Sandia notes that inverters often have short surge capabilities four to six times their rated output, for a few seconds, to start motors. Its guide suggests time-delay fuses for battery circuits, though it says some designers get good results with fast-acting Class T fuses. The manual tells you which type your inverter expects.

Inverter fuse size chart: what to look up instead

Rather than a chart of fuse sizes, here is what to find before you buy one:

What to findWhereWhy it matters
Continuous output wattsLabel and manualSets the full-load DC current
DC input voltageLabelA 12 V inverter draws twice the current of a 24 V one at the same watts
Recommended fuse size and typeInstallation section of the manualThe number to use
Recommended cable size and maximum lengthManualThe fuse must not exceed the cable's ampacity
Battery maximum discharge currentBattery manual or BMS specificationsThe book says to respect the BMS limits of the weakest battery

Scale makes a difference. Sandia notes that a 2,000 W inverter on 12 V can draw more than 235 amps. The book's 300 to 600 W class draws a fraction of that, which is one more reason to size the inverter honestly; see what size inverter do I need.

Class T or ANL?

The book allows either. The difference that matters is the interrupt rating: how much current a fuse can safely stop in a dead short. The Florida Solar Energy Center (FSEC) warns that batteries can deliver thousands of amperes under short-circuit conditions, and that an overcurrent device with too low an interrupt rating could fail with disastrous results.

Sandia gives a sense of scale: a single 6-volt, 220 amp-hour lead-acid battery may produce as much as 8,000 amps for a fraction of a second, and two paralleled batteries nearly twice as much. It notes that listed, DC-rated current-limiting class fuses normally have interrupt ratings up to 20,000 amps, and that Class T fuses with DC ratings can be used at the battery.

So the cautious choice for a large or paralleled battery bank is a DC-rated Class T fuse. For a small system, use the type your inverter and battery manuals call for, and check its DC interrupt rating either way.

Where the inverter fuse goes

The full hookup, step by step, is in how to connect an inverter to a battery.

When an inverter fuse blows

Never replace it with a bigger one. A fuse that blows is reporting a problem:

Before you install the new fuse, open the disconnect, look at the fuse holder for discoloring or melted plastic, and feel the cable ends for heat after the next load test. A holder that has been cooked once will do it again. Replace it with the same type and rating once the cause is fixed. If you add batteries or a bigger inverter, Project 24's rule applies: resize the master fuse and cables to the new maximum draw, and recheck the cable with our 12 V wire gauge guide. The battery side of the system starts with the DIY LiFePO4 battery box.

Frequently asked questions

What size fuse do I need for my inverter?

Use the fuse size and type in your inverter's manual for your battery voltage. Manuals base it on the inverter's full-load DC current plus headroom, and the fuse must never exceed the ampacity of the cable. Install it on the positive cable within inches of the battery terminal.

How do you calculate an inverter fuse size?

Divide the inverter's continuous watts by the low battery voltage times its efficiency to get full-load DC current. Sandia's example: 2,500 W at 22 V and 85% efficiency draws 134 amps, and the cable must carry 125% of that, 167 amps. The fuse sits between those limits, as the manual specifies.

Should I use a Class T or ANL fuse for an inverter?

The Off-Grid Handbook allows either. The key difference is interrupt rating, how much short-circuit current a fuse can safely stop. Sandia notes DC-rated current-limiting class fuses reach 20,000 amps, so Class T is the cautious choice for large or paralleled battery banks. Follow your inverter and battery manuals.

Can I use a bigger fuse if my inverter fuse keeps blowing?

No. A fuse larger than the cable's ampacity leaves the cable unprotected. A blowing fuse points to a short, an overload or a loose, overheating connection. Find and fix the cause, then replace the fuse with the same type and rating.

Sources

Safety guidance changes. Check the agency pages above for the current version, and follow your local code and manufacturer instructions.